RS-485 connectivity and wiring

For pool owners wiring a server to an Aqualink RS control panel. This covers the physical RS-485 link and the CLI options that select it. Full option detail lives in Configuration reference.

Before Aqualink Automate can talk to a pool controller, you need a physical RS-485 connection between the control panel and the server running the software. This document explains the two supported transports, the command-line options that select them, and how to wire the adapter to the panel.

Note: Both supported RS-485 protocols — Jandy/Zodiac and Pentair — ride the same physical connection. The transport is protocol-agnostic; the software auto-detects which protocol is on the bus. See the supported-equipment summary for the equipment covered.

Contents

Serial connectivity overview

There are two ways to connect the server to the RS Aqualink panel:

  • USB-RS485 adapter — the cheapest and most direct option. A USB-to-RS485 adapter plugs into the server over USB and into the panel's RS-485 terminals over wire. The software talks to it through a local serial port (--serial-port).
  • Serial-over-ethernet adapter — for installations where the server is far from the panel. A serial-to-ethernet adapter sits at the panel, and the server reaches it over the network (--remote-serial-port). This is useful when you cannot run a USB cable the full distance.

The two transports map to two implementations in the code: PhysicalSerialPortImpl for the local USB serial port, and NetworkSerialPortImpl for the TCP/RFC2217 network port (RFC2217 itself is handled by a separate protocol component). You select one or the other on the command line; they are mutually exclusive — passing both --serial-port and --remote-serial-port is rejected as a conflict.

In both cases the line is configured at 9600 baud, 8 data bits, no parity, 1 stop bit, no flow control (9600 8N1). These settings are fixed in the code to match the Aqualink RS bus and are not user-tunable.

Config-file keys are the option long name without the leading dashes. For example, the CLI flag --serial-port is written serial-port in a config file, and --remote-serial-port is written remote-serial-port.

Connecting a USB-2-RS485 adapter

Use --serial-port (short form -s) to point the software at the local serial device the adapter enumerates as.

Option Short Type Default Description
--serial-port -s string /dev/ttyS0 (POSIX), COM1 (Windows) Local serial device for the RS-485 connection.

Note: The default is a platform value resolved at runtime: /dev/ttyS0 on Linux and macOS, COM1 on Windows. These are placeholder defaults — a real USB-RS485 adapter usually enumerates as /dev/ttyUSB0 on Linux or a COMn port (for example COM3) on Windows, so you will almost always set this explicitly.

A --baudrate option exists but is currently ignored — the bus is always opened at 9600 8N1, no flow control (serial_initialise.cpp hardcodes it and never reads the setting). Parity, data bits, stop bits and flow control have no options at all.

Worked examples

Linux:

aqualink-automate --serial-port /dev/ttyUSB0   # typical USB-RS485 device on Linux

Windows:

aqualink-automate --serial-port COM3   # the COM port your adapter enumerated as

The equivalent config file (examples/config-serial.conf):

# Physical RS-485 serial port
serial-port = /dev/ttyUSB0

Run it with:

aqualink-automate --config config-serial.conf

Connecting a serial-over-ethernet adapter

Use --remote-serial-port (short form -r) with a host:port target to reach a serial-to-ethernet adapter over the network. When --remote-serial-port is set to a non-empty value, the software uses the network transport instead of a local serial port.

Option Short Type Default Description
--remote-serial-port -r string (unset) Remote serial endpoint as host:port. Selects the network transport when non-empty.
--rfc2217 flag on by default (only applies to remote ports) Use the RFC2217 telnet serial protocol.
--no-rfc2217 flag off Disable RFC2217 and use a plain socket.
--rawtcp flag off Use raw TCP for the remote serial port.

Behavior:

  • A remote port uses RFC2217 by default. Many serial-to-ethernet adapters speak RFC2217, which carries serial line settings over the connection.
  • Pass --no-rfc2217 to fall back to a plain socket if your adapter does not support RFC2217.
  • Pass --rawtcp to use raw TCP.
  • These choices conflict with each other. --rfc2217 cannot be combined with --rawtcp or --no-rfc2217, and --no-rfc2217 cannot be combined with --rawtcp; the software rejects contradictory combinations at startup.

Worked examples

RFC2217 (the default — shown explicitly here):

aqualink-automate --remote-serial-port 192.168.1.50:8899 --rfc2217

Plain socket (adapter without RFC2217 support):

aqualink-automate --remote-serial-port 192.168.1.50:8899 --no-rfc2217

Raw TCP:

aqualink-automate --remote-serial-port 192.168.1.50:8899 --rawtcp

The equivalent config file (examples/config-network.conf):

# Remote serial (host:port)
remote-serial-port = 192.168.1.50:8899
rfc2217 = true

Run it with:

aqualink-automate --config config-network.conf

To capture traffic from a live network connection for later replay, see Recording and replay.

Serial connection guide — the wires

Important: This section is hardware-installation field guidance based on common RS Aqualink installations. It is not derived from the software and the software cannot verify your wiring. Always consult your pool equipment manual for the labeling specific to your panel.

  1. Identifying connections: The simplest configuration is to connect the Data+ and Data- from a USB-2-RS485 adapter to the Data+ and Data- lines of the RS-485 interface of the RS Aqualink panel.
  2. Cabling: Standard RS485 pool equipment cable includes 4 wires — Data+, Data-, Power+, and Ground-. Wire colors may vary depending on your installation, and labeling has evolved over the years. We recommend consulting your pool equipment manual for accurate information.
  3. Connecting to the control panel: The control panel usually has a 4-post connector at the top right (some might have 2). This is the RS485 interface. Although the wires will be labeled, they won't indicate their functionality. The most common configuration is Green, Yellow, Black, Red.

Note that some USB adapters might have 3, 4, or even 6 connections. The third connection is typically used for ground (which can be crucial or problematic depending on your specific setup), and the fourth one is typically used for power and should not be used with USB-2-RS485 adapters.

RS Aqualink wiring most commonly uses the Green, Yellow, Black, Red color configuration. These wires are found at the top of the RS Aqualink panel. When following the standard color configuration, the table below shows the typical installation:

Wire colour USB-2-RS485 pin Description Function
Black Pin A Data+ Data signaling line (+ve)
Yellow/White Pin B Data- Data signaling line (-ve)
Green GND Ground Common/shared ground line
Red Not Used Power Not Used

Note that the ground may be considered optional, as RS-485 is a differential signal (no common ground is required). Adding that third wire between the server and panel may still be done to limit the common-mode voltage and help with noise suppression.

Wiring and cabling recommendations

Important: This section is hardware-installation field guidance, not derived from the software.

The wiring and connections to the adapter and panel are critical to getting a good signal. Many issues with poor message checksums — that is, lots of rejected messages — usually occur due to wiring problems. The recommended wire is 24AWG twisted pair; below is a paragraph taken from RS Cable Selection:

The RS-422 specification recommends 24AWG twisted pair cable with a shunt capacitance of 16 pF per foot and 100 ohm characteristic impedance. While the RS-485 specification does not specify cabling, these recommendations should be used for RS-485 systems as well.

See also